38Y129
Pneumatic T-Stat, Dual Pressure Temp, 0-25
Return Air Sensor
Return Air Temperature Sensor, Averaging, Liquid Filled Element For Duct Mounting, Temp Sensing Range 0 to 200 F, Standard Insertion 222 In, Height 3 In, Width 1 7/8 In, Depth 222 In, One Pipe Direct Acting Temp Sensor, For Use With 3UC59, 3UC60, Provide Proportional Control of Pneumatic Valves and Actuators, Max Safe Operating Temp 225 F, Push On Barb For 5/32 and 1/4 In OD Tubing Air Connections, Duct Mounting, Includes Installation Instructions
Артикул:
3UC08
Каталог:
Grainger
Производитель:
HONEYWELL
Номер модели:
LP915A1044
Страна производства:
USA
Вес (кг):
0.77
Спецификация:
Item: Pneumatic Temperature Transmitter |
Type: 1-Pipe, Duct Mount, Liquid Filled Capillary |
Control Range: 3 to 15 psi |
Air Connections: Push-on Barb for 5/32 and 1/4 O.D. Tubing |
Contact Action: DA |
Element Type: Liquid-Filled Capillary |
Capillary Length (In.): 222 |
Max. Safe Air PSI: 25 |
Max. Safe Operating Temp. (F): 225 |
Height (In.): 3 |
Width (In.): 1-7/8 |
Depth (In.): 2-21/32 |
Max. Ambient (F) Bulb Direct: 225 |
Control Range (F): 0 to 200 |
Remarks: Averaging Proportional, Duct-Mounted, Sensing Range Nonadjustable, (0 to 200F) |
Air Consumption (SCFM): 0.019 |
Throttling Range: 3 to 15 PSI |